Structure and function
30
Building Technologies
A6V10099837_a_en
Fire Safety & Security Products 12.2007
Ref. Identification Access
level
Function
KEY1 Silence
Re-sound
horn
2 Deactivation/activation of monitored control line 1 and, depending on programming also control
line 2 or 5 (blocked in state "Activated" until state "Released" occurs and while timer is running)
Also used from access level 3 to select the programming steps (see chapter 11.6)
KEY2 Mode select 2 Switching mode between:
Not blocked or "Autom. & Manual" (ready to operate)
"Autom. blocked" or "Manual only"
"Autom. & Man. blocked"
Also used from access level 3 to select the programming steps (see chapter 11.6)
KEY4
to
KEY7
Operating access 1 Enabling of access level 2 (enter digits "4233")
Also used from access level 2 for:
Trigger "Horn test" (see chapter 10.4)
Trigger "Warning panel test" (see chapter 10.5)
Switch to "Program user functions" mode (see chapter 11)
Access to "Performing system test" (see chapter 10.7)
Access to "Reset user functions to default or application settings" (see chapter 11.4)
KEY8 - - Not used (factory setting)
KEY9 Lamp test 1 Pressing the key activates all LEDs and buzzer for 5 seconds (see chapter 10.2)
Also used from access level 2 for:
Trigger "Horn test" (see chapter 10.4)
Trigger "Warning panel test" (see chapter 10.5)
KEY10 System test 2 System setting in mode "System test"
2
)
Possible only after previous input of a code (see chapter 10.7)
KEY11 Disable/
Enable
2 Disabling of horn, actuator and fire control:
First pressing disables horn and actuator (monitored control lines 1 and 4), and possibly 2
and 5 if these lines are programmed as horn or actuator (see step 1 and step 3)
3
)
Second pressing disables fire control (driver outputs 2, 8 and 1 and possibly control line 2 or
5. If these monitored control lines are programmed as fire control, see step 1 and 3
4
)
Third pressing disables both
Fourth pressing enables both
Disabling is not possible while the system is in the "Activated" condition
Disable/
Enable
2 Disabling of "RT-alarm" and "RT-fault" (inoperable if no remote transmission device is used):
First pressing disables contact 2 "RT-fault"
Second pressing disables contact 1 "RT-alarm" and control line 2 if step 3 option 17
Third pressing disables both
Fourth pressing enables both
KEY12
Not used -
Alternative (step 3 = option 14): Inoperable
2
) Monitored control line 5 only when in programming step 1 options 14 and 15 are set (see chapter 11.6.1)
3
) Driver outputs: only when in programming step 16 options 9, 18 and 20 are set (see chapter 11.6.16)
4
) Control line 5 only when in programming step 1 option 17 is set, control line 3 only if programming step 3 option 18 or 19 (see chapter
11.6.1)
ZONES
disable/
enable
2 Disabling of detector zones 1 to 3 and manual release:
First pressing disables detector zone 1
Second pressing disables detector zone 2
Third pressing disables detector zone 1 and 2
Fourth pressing disables detector zone 3
Fifth pressing disables manual release
Sixth pressing disables zones 1 to 3 and manual release
Seventh pressing enables zones 1 to 3 and manual release
Also used from access level 3 to select the options in programming steps (see chapter 11.6)
KEY13
Not used -
Alternative (step 11 = option 3): Inoperable
ZONES
det. test/
enable
2 Setting of the zones 1 to 3 and manual release to "Test mode":
First pressing sets zone 1 to "Test mode"
Second pressing sets zone 2 to "Test mode"
Third pressing sets zones 1 and 2 to "Test mode"
Fourth pressing sets zone 3 to "Test mode"
Fifth pressing sets zone 1 to 3 to "Test mode"
Sixth pressing sets manual release to "Test mode"
Seventh pressing sets zones 1 to 3 and manual release to "Test mode"
Eighth pressing sets zones 1 to 3 and manual release to "Normal mode"
Also used from access level 3 to select the options in programming steps (see chapter 11.6)
KEY14
Not used -
Alternative (step 11 = option 3): Inoperable
Silencing the buzzer upon alarm and fault
Also deactivates contact 2 "RT-fault" if step 3, option 8 is selected
1
Alternative (step 13 = option 4): Silencing the buzzer upon alarm and fault and silencing horn
upon fire alarm
KEY15 Silence buzzer
2
Alternative (step 12 = option 5): Only accessible on access level 2
Also used from access level 3 to select the options in programming steps (see chapter 11.6)
Reset of the system upon alarm
Not available in the state "Activated" and as long as the valve control is active (flooding time)
Alternative (step 9 = option 12): Reset is not available as long as zone 4 is an alarm or
monitored input 1 is in state "active 1" or control line 1 (horn) is activated
KEY16 Reset 2
Alternative (step 13 = option 8): Also to reset fault
Also used from access level 3 to select the options in programming steps (see chapter 11.6)