–
Option 12: "Alarm" zone 1 and zone 2 and zone 3 trigger "Activated" condition
and "Alarm" zone 1 or zone 2 or zone 3 or any of 2 zones triggers
"Fire alarm"
–
Option 13: On "Alarm" zone 3, fire controls, fire alarm (LED6), horn lines
activated.
Details on programming, see chapter 11.6.11.
Detector line 4
Detector line 4 is provided for connecting a manual activation button. This button is
used for manual activation of extinguishing.
Connectable manual activation buttons:
–
Conventional manual activation buttons with 5.6 V Z-diode and LED in line
–
Conventional manual activation buttons with 820 Ω resistor
For configuration of the type selection, see chapter 5.3.1.
As a rule, manual activation buttons with a yellow housing, e.g. DM1103-L, must
be used.
Fig. 23 Detector line 4 for manual activation