In addition to the weekly test specified previously, the following inspection and testing
procedures should be carried out each month:
a. Check all battery terminals and electrolyte levels, where appropriate. Maintain all
batteries in a serviceable condition.
b. Check condition of battery enclosure for corrosion and ensure the batteries are stored in a
safe and secure condition.
c. Check that all visual indicators operate correctly, including those on mimic or repeater
panels.
d. Check the operation of all aural and visual indicators external to the control and
indicating equipment.
e. Simulate fault conditions on all alarm zones to ensure that fault indicators, both aural and
visual where applicable, are operating correctly from each alarm zone facility.
f. Check that all control and indicating equipment is in a clean and operational condition,
and effectively dust-sealed.
g. Ensure that all fire indicator panels, sub-indicator panels, repeater panels, and mimic
panels, are clearly visible and readily accessible (see AS1670).
h. Ensure that all controls are returned to the normal condition.
i. Record the results of all monthly maintenance procedures in the logbook, including all
items requiring corrective action, adjustment, and the like.
j. Check that items previously recorded as requiring attention have been attended to, or
record the reason why corrective actions have not been completed.
Monthly Tests
Procedure
firealarmresources.com

Table of Contents

Other manuals for Simplex 4100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100 and is the answer not in the manual?

Simplex 4100 Specifications

General IconGeneral
TypeFire Alarm Control Panel
ManufacturerSimplex
Model4100
Network CapabilityYes
AddressableYes
Power Supply120/240 VAC, 50/60 Hz
DisplayLCD
Annunciator SupportYes
Battery BackupYes
Releasing CapabilityYes
Max DevicesDepends on configuration
Max Notification Appliance Circuits (NAC)Varies with configuration
Max Releasing CircuitsVaries with configuration
Max Remote AnnunciatorsVaries with configuration
Communication PortsMultiple
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
NAC Outputs4 (expandable)
NetworkingYes

Related product manuals