Parameter list – Program 081: S4 ActiveCore Series
081 - SET0 - ActiveCore Top/Bottom Mount
Revision: 1.1
This sheet is only for use in SKOPE product(s) ActiveCore Top & Bottom Mount
Controller Type SKOPE S4
Controller Model & Revision PZSKC0H001K (Rev 1.211)
SKOPE Part Number
Probe measurement stability
Select °C/°F (0 = °C, 1 = °F)
/C1 0.0 °C/°F C -12.7°C 12.7°C
/C2 0.0 °C/°F C -12.7°C 12.7°C
rd 2.0 °C/°F C 0.0°C 19°C
r1 1.0 °C/°F C -50.0°C r2
Night Mode set point delta
r5 2.0 °C/°F C 0°C 19.0°C
Automatic Day to Night Mode: Time Period with Door Closed
Automatic Night to Day Mode: Time Period in Night mode
Time allowed for door closure after entering Night mode via keypad
CCt 2.0 °C/°F H 0.1°C 20.0°C
CCP Mode: Temperature Delta
c0 1 min C 0 200 Compressor start delay on power-up
c1 0 min C 0 100 Minimum time between consecutive compressor starts
c2 5 min C 0 100 Minimum compressor off time
c3 5 min C 0 100 Minimum compressor on time
c4 7 min C 0 100 Compressor on time with duty setting
d0 1 - C 0 2 Type of defrost
dI 2 hrs C 0 199 Compressor Runtime between Defrosts
dt 4.5 °C/°F C -50.0°C 127°C Defrost Termination Temperature
dP 90 min C 1 199 Maximum defrost duration
d4 1 - C 0 1 Defrost when switching the instrument on (0:no 1:yes)
d5 0 min C 0 199 Defrost delay on power-up (when d4=1)
d6 1 - C 0 1 Freeze temperature display during defrost
dd 0 min C 0 15 Dripping time
d8 0 hrs C 0 15 Bypass high and low temperature alarms (AH,AL) after defrost
d9 0 - C 0 1 Defrost priority over compressor protectors
d/ - °C/°F C - - Defrost probe reading
d10 -10.0 °C/°F C -50.0°C 127°C Start defrost condition: evaporator temperature threshold
d11 127 °C/°F H -50.0°C 127°C Enabling defrost condition: Control probe threshold
d12 200 min C A10 200 No Downward Tendency Defrost - Start Delay
d20 20 min H 0 200 Sample time of Tendency evaluation (minutes)
d21 1 - H 1 5 Number of allowed defrost before RSF alarm
d22 0.1 °C/°F H 1.0°C 5.0°C Temperature gap of Tendency evaluation (°C/°F)
A0 2.0 °C/°F C -20°C 20°C Temperature Alarm Differential
AL 4.0 °C/°F C
Low Temperature Alarm Setpoint. (Absolute if A0
AH 8.0 °C/°F C -50°C 150°C High Temperature Alarm Setpoint. (Absolute if A0≤0, relative A0>0)
Ad 180 min C 0 199 Temperature Alarm Delay
A10 2 min C 0 10 Open Door Alarm Delay
F0 3 sec C 1 100 Start delay when FAN ON is required by the Regulation
Fd0 100 min C 1 100 Fan DAY Duty Cycle : ON time
FdF 1 min C 1 100 Fan DAY Duty Cycle : OFF time
Fn0 2 min C 1 100 Fan NIGHT Duty Cycle : ON time
FnF 2 min C 1 100 Fan NIGHT Duty Cycle : OFF time
H0 1 - C 0 207 Supervisor Serial address
H4 0 - C 0 1 Disable buzzer
H5 81 - C 0 199 ID code (read-only)
Warning:
1. Only make program modifications with reference to relevant Operating Manual.
2. This parameter sheet is exclusively for SKOPE refrigeration systems with its dedicated Carel controller.
3. Any alteration from this program may adversely affect the SKOPE Refrigeration System operation.
4. Specification may change without notice. Please check with Skope Customer Service for latest version.
15 April 2016
Electronic Controller Parameter Sheet
Parameter
Last Revised on
081
Full List
SET0
CPS1016-081-SET0