No.EX※※-OMS0027
•Analogue output unit parameters (1)
No. Parameter Definition Item Content
Default
setting
Parameter
setting range
Enable Generates an error.
1
The power
supply short
circuit
detection for
the output
device
Generates error
when the short
circuit of the output
device is detected.
Disable
Does not generate an
error.
Unit
0..10 V
0..5 V
1..5 V
0..20 mA
2
Analogue
output range
Sets the range of
the analogue output
device.
4..20 mA
Selects the analogue
output range.
0..10 V
Channel
Offset binary Offset binary.
Sign &
Magnitude
Signed binary.
2s complement 2’s complement.
3
Analogue
data format
Sets analogue data
type which is
output to PLC.
Scaled Scale conversion type.
Unit
Enable Generates an error.
1
User setting
value upper
limit error
Generates error
when the output
value exceeds the
set value.
Disable
Does not generate an
error.
Enable
Generates an error.
Val: -32766 to 32767
4
Scale upper
limit setting
Sets the scale
upper limit.
Generates error
when the output
value exceeds the
upper limit.
Disable
Does not generate an
error.
Val: -32766 to 32767
Val: 1000
Channel
Enable Generates an error.
1
User setting
value lower
limit error
Generates error
when the output
value falls bellow
the set value.
Disable
Does not generate an
error.
Enable
Generates an error.
Val: -32767 to 32766
5
Scale lower
limit setting
Sets the scale
lower limit.
Generates error
when the output
value falls below
the lower limit.
Disable
Does not generate an
error.
Val: -32767 to 32766
Val: 0
Channel
Enable
Output will be user fault
value.
1
6
Output setting
for
communication
error
2
Sets output when
communication
error is occurred.
Disable
Output will be held last
state.
Channel