-55-
No.EX※※-OMS0027
•Analogue I/O unit parameters (2)
No. Parameter Definition Item Content
Default
setting
Parameter
setting range
.
Enable Generates an error.
1
User’s set
value lower
limit error
Generates error
when the input or
output value falls
below the lower
limit.
Disable
Does not generate an
error.
Enable
Generates an error.
Val: -32767 to 32766
8
Scale lower
limit setting
Sets the scale
lower limit.
Generates error
when the input or
output value falls
below the lower
limit.
Disable
Does not generate an
error.
Val: -32767 to 32766
Val: 0
Channel
Enable
Output will be user fault
value.
1
9
Output setting
for
communication
fault
2
Sets output when
communication
error is occurred.
Disable
Output will be held last
state.
Channel
Enable
Output will be user idle
value.
1
10
Output setting
for
communication
idling
2
3
Sets output during
communication
idling.
Disable
Output will be held last
state.
Channel
1: Set value shall be set per analogue output range within settable range in the table below.
When the analogue output range is changed, check the set value and change it to an appropriate value.
2: This function is valid only when "Hold/Clear priority" of the system parameter is set to "Via software".
3: Some PLC does not support an idle mode.