8-6
Cn038 Communication Protocol
Initial Value Unit Setting Range Effective RS-485 Address
0 --
0 ~ 8 Power Re-set 0029H
Setting Description:
Setting Description Setting Description
0 7 , N , 2 ( Modbus , ASCII ) 5 8 , O , 1 ( Modbus , ASCII )
1 7 , E , 1 ( Modbus , ASCII ) 6 8 , N , 2 ( Modbus , RTU )
2 7 , O , 1 ( Modbus , ASCII ) 7 8 , E , 1 ( Modbus , RTU )
3 8 , N , 2 ( Modbus , ASCII ) 8 8 , O , 1 ( Modbus , RTU )
4 8 , E , 1 ( Modbus , ASCII ) -
Cn039 Communication Timeout Setting
Initial Value Unit Setting Range Effective RS-485 Address
0 sec 0 ~ 20 Power Re-set 002AH
Setting Description: If the setting value is greater than 0, the communication timeout function is turned
on immediately and must conduct communication within the set time, otherwise, a
communication error will appear. If the setting value is 0, then indicates this
function is turned off.
Cn040 Communication Response Delay Time
Initial Value Unit Setting Range Effective RS-485 Address
0 0.5ms 0 ~ 255 Power Re-set 002BH
Setting Description: Delay the communication time of driver responding to supervisory control unit.