Chapter 7 Swing Arm Setup and Operation (Excluding SMP)
239
Firmware Version 3/4.31.37
Relay Pin
Primary Bay FCMs
Swing Arm FCMs
Secondary Bay FCMs
1
J3-4 (TDB)
X
X
2
J3-3 (TDA)
X
X
3
J3-2 (RDB)
X
X
4
J3-1 (RDA)
X
X
5
X
X
J3-4 (TDB)
6
X
X
J3-3 (TDA)
7
X
X
J3-2 (RDB)
8
X
X
J3-1 (RDA)
9
X
J3-4 (TDB)
X
10
X
J3-3 (TDA)
X
11
X
J3-2 (RDB)
X
12
X
J3-1 (RDA)
X
Relay Coil
13
X
X
common
Relay Coil
14
X
X
+24 VDC or 115 VAC
Via Swing Arm Switch
85
13
9
12
14
1
4
Relay Socket
Swing Arm FCMs
Communication Switching
Relay Socket-Square D- Part # 8501NR45
Relay-Square D-Part # 8501RSD34V53
Figure 7.2 Swing Arm FCM Relay Socket