E6582233
H-9
8 8
Output voltage: The voltage displayed is the output command voltage. 100% reference
value is 400V on 400V models.
This unit can be switched to V (volts).
Torque current: The reference value (100% value) is the rated output current indicated on
the nameplate. The current required to generate torque is calculated from
the load current by vector operations. The value thus calculated is
displayed.
Load factor of inverter: Depending on the PWM carrier frequency (f300) setting and so on, the
actual rated current may become smaller than the rated output current
indicated on the nameplate. With the actual rated current at that time (after
a reduction) as 100%, the proportion of the load current to the rated
current is indicated in percent. The load factor is also used to calculate the
conditions for overload trip (
).
Note 11: Status monitor of * mark is displayed by
to and setting.
The left side character is as following table by each parameter setting number.
Paramete
Settin
No. LED displa
Function Unit
to ,
0
x50.0
Operation frequenc
Hz / free uni
1
c16.5
Output curren
% /
2
f50.0
Frequenc
settin
value Hz / free uni
to
3
y100
Input volta
e
DC detection
% / V
4
p 90
Output volta
e
command value
% / V
5
k 3.0
Input powe
kW
6
h 2.8
Output powe
kW
7
q 80
Tor que %
8
w 90
Torque curren
% /
9-11 - - -
12
b40.0
Frequency setting value (after
compensation)
Hz / free unit
13-17 - - -
,
18 **** Arbitrar
code from communication -
to
19-22 - - -
23
d40.0
PID feedback value Hz / free uni
24-26 - - -
27
l 70
Drive load facto
%
to ,
28-33 - - -
34
n89.0
Number of startin
10000 times
35-51 - - -
52
w50.0
During stop : Frequency setting value
Durin
operation : Operation frequenc
Hz / free unit