Page 31 of 39    Rev. 13 
3.5 CHARGER COMMON PARAMETERS SET UP 
 
  3.5.1 GENERAL 
 
Select (function 3), Operate (function 4), Direct operation (function 5), Direct operation no acknowledge, with Object 41 
variation 01 or 02, allows to modify the charger operating parameters. 
In this paragraph, we present the most common charger settings. For more information, please contact the factory. 
All points are coded in 16 bits. 
Only qualified and trained personnel can access this mapping. 
Parameters modification with wrong information may lead to major defects and failures if wrong data is used. 
 
 
  3.5.2 VOLTAGE OR CURRENT SETTINGS 
 
In order to modify the float voltage, write the required value in point 1 (Refer to Note1, for the byte format to send). 
For equalize voltage, the point 2 is to be used. 
In order to modify the float current limit, write the required value in point 3 (Refer to Note1, for the byte format to send). 
For equalize current limit, the point 4 is to be used. 
 
  3.5.3 CHARGER CONFIGURATION  
 
Please do not modify this register without consulting the factory. To modify the charger configuration, write the required 
value in point 5, the byte format to send is the following: 
 
           MSB                       LSB 
15 14 13 12 11 10  9 8 7 6 5 4 3  2  1 0
 
 
0:        ON/OFF display 
1:        Load sharing  
2:        Temperature compensation 
3:        AC current display 
4:        AC voltage display 
5:        LCD sleep mode 
6:        Language 
7:        Battery current display 
8         Formation 
9:        Battery test 
10:      x 
11:      x 
12:      x 
13:      x 
14:      x 
15:      x 
 
 
  3.5.4 ALARM RESET  
 
To reset all alarms, send (01 in binary) into the point 90L.