BATTERY CHARGER USER’S MANUAL PART- 2: THEORY OF OPERATION
MCEnPC23-REV.2.4 Page 38
iii. Current Post-Charge Mode (optional)
If this option is enabled, the battery charger will revert back from Equalize to Float mode when Load current reaches
a preset value between 5% and 95% of Equalize current limit value, during a preset time between 1 and 8191
minutes. We can enable or disable Current Post-Charge as shown on the procedure below:
Control?
Ok
Next
P
r
Exit
Adjust? Level1
Ok
Next
P
r
Exit
Eq Stop
Set
Exit
Next
P
r
ON IPostChg
Set
Exit
Next
P
r
ON
OFF
Next
Exit
:getyou Next till Press
:getyou Next till Press
Delay
mn 30
Next
Exit
-
ON IPostChg
Next
Exit
-
% 5 IPostChg
Figure 42 : Procedure to set Current Post-Charge parameters to Stop Equalize mode.