BATTERY CHARGER USER’S MANUAL PART- 2: THEORY OF OPERATION
MCEnPC23-REV.2.4 Page 40
v. Capacity Post-Charge Mode (optional)
When the Capacity Post-Charge is selected, the charger will revert back from Equalize into the Float mode when the
battery Capacity reaches its preset value, during a preset time between 1 and 8191 minutes. We can enable or disable
Capacity Post-Charge as shown on the procedure below:
Control?
Ok
Next
P
r
Exit
Adjust? Level1
Ok
Next
P
r
Exit
Eq Stop
Set
Exit
Next
P
r
ON CapPostChg
Set
Exit
Next
P
r
ON
OFF
Next
Exit
:getyou Next till Press
:getyou Next till Press
Delay
mn 30
Next
Exit
-
ON CapPostChg
Next
Exit
-
95% CapPostChg
Figure 44 : Procedure to set Capacity Post-Charge parameters to Stop Equalize mode.