EasyManuals Logo

Unipower ARR-M Series User Manual

Default Icon
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
BATTERY CHARGER USER’S MANUAL PART- 2: THEORY OF OPERATION
MCEnPC23-REV.2.4 Page 56
vii. Rectifier High Voltage Alarm *
Rectifier High Voltage alarm is activated if the charger output voltage exceeds a preset value during a preset time.
We can enable or disable and adjust Rectifier High Voltage Alarm as shown on the procedure below:
Alarms?
Ok
Next
Pr
Exit
Adjust? Level1
Ok
Next Pr
Exit
ON 142.3V HVAL2
Set
ExitNext
Pr
ON
OFF
Next
Exit
:getyou Next till Press
Next
Exit
-
VoltHigh Rect
10.5A 143.0V
:getyou Next till Press
ON 142.3V HVAL2
ON HVAL2
Figure 56 : Rectifier High Voltage Alarm adjustments procedure.
* : Included, enabled upon customer request only. Can also be field activated
** : Optional

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Unipower ARR-M Series and is the answer not in the manual?

Unipower ARR-M Series Specifications

General IconGeneral
BrandUnipower
ModelARR-M Series
CategoryBattery Charger
LanguageEnglish