BATTERY CHARGER USER’S MANUAL PART- 2: THEORY OF OPERATION
MCEnPC23-REV.2.4 Page 56
vii. Rectifier High Voltage Alarm *
Rectifier High Voltage alarm is activated if the charger output voltage exceeds a preset value during a preset time.
We can enable or disable and adjust Rectifier High Voltage Alarm as shown on the procedure below:
Alarms?
Ok
Next
Pr
Exit
Adjust? Level1
Ok
Next Pr
Exit
ON 142.3V HVAL2
Set
ExitNext
Pr
ON
OFF
Next
Exit
:getyou Next till Press
Next
Exit
-
VoltHigh Rect
10.5A 143.0V
:getyou Next till Press
ON 142.3V HVAL2
ON HVAL2
Figure 56 : Rectifier High Voltage Alarm adjustments procedure.
* : Included, enabled upon customer request only. Can also be field activated
** : Optional