EasyManua.ls Logo

Unipower ARR-M Series - Nd Low Volt Level); Rectifier Low Voltage Alarm

Default Icon
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BATTERY CHARGER USER’S MANUAL PART- 2: THEORY OF OPERATION
MCEnPC23-REV.2.4 Page 58
ix. Rectifier Low Voltage Alarm *
Rectifier Low Voltage alarm is activated if the rectifier voltage decreases below a preset value during a preset time.
We can enable or disable and adjust Rectifier Low Voltage Alarm as shown on the procedure below:
Alarms?
Ok
Next
Pr
Exit
Adjust? Level1
Ok
Next Pr
Exit
ON 115.5V LVAL2
Set
ExitNext
Pr
ON
OFF
Next
Exit
:getyou Next till Press
Next
Exit
-
ON 115.5V LVAL2
ON LVAL2
Volt Low Rectif
10.5A 114.7V
:getyou Next till Press
Figure 58 : Rectifier Low Voltage Alarm adjustments procedure.
* : Included, enabled upon customer request only. Can also be field activated
** : Optional

Table of Contents