BATTERY CHARGER USER’S MANUAL PART- 2: THEORY OF OPERATION
MCEnPC23-REV.2.4 Page 58
ix. Rectifier Low Voltage Alarm *
Rectifier Low Voltage alarm is activated if the rectifier voltage decreases below a preset value during a preset time.
We can enable or disable and adjust Rectifier Low Voltage Alarm as shown on the procedure below:
Alarms?
Ok
Next
Pr
Exit
Adjust? Level1
Ok
Next Pr
Exit
ON 115.5V LVAL2
Set
ExitNext
Pr
ON
OFF
Next
Exit
:getyou Next till Press
Next
Exit
-
ON 115.5V LVAL2
ON LVAL2
Volt Low Rectif
10.5A 114.7V
:getyou Next till Press
Figure 58 : Rectifier Low Voltage Alarm adjustments procedure.
* : Included, enabled upon customer request only. Can also be field activated
** : Optional