BATTERY CHARGER USER’S MANUAL PART- 2: THEORY OF OPERATION
MCEnPC23-REV.2.4 Page 70
xxi. Battery High Current Alarm **
Battery High Current alarm is activated if the current provided from battery to load exceeds the preset value during a
preset time. We can enable or disable and adjust this alarm as shown on the procedure below:
Alarms?
Ok
Next
P
Exit
Adjust? Level1
Ok
Next P
Exit
ONA 75.0IHBat
Set
ExitNext
P
ON
OFF
Next
Exit
:getyou Next till Press
Next
Exit
-
ON IHBat
tHighCurrenBatt
10.0A 136.2V
:getyou Next till Press
ONA 75.0IHBat
Figure 70 : Battery High Current Alarm adjustments procedure.
* : Included, enabled upon customer request only. Can also be field activated
** : Optional