BATTERY CHARGER USER’S MANUAL PART- 2: THEORY OF OPERATION
MCEnPC23-REV.2.4 Page 29
iii. LowVoltageEqualize(optional)
If the Low Voltage Equalize is enabled, then the charger will go into “Equalize” mode whenever the DC output
voltage drops under a preset voltage. The duration is adjustable between 1 and 8191 hours. We can enable or disable
and adjust low volt Equalize as follows:
Control?
Ok
Next P
r
Exit
Adjust? Level1
Ok
Next P
r
Exit
EqStart
Set
ExitNext
P
r
ON 120.0V LVEq
Set
Exit
Next
P
r
Next
Exit
ON
OFF
Out Time
Next
Exit
08
H
:getyou Next till Press
:getyou Next till Press
Next
Exit
-
-
ON 120.0V LVEq
ON LVEq
Figure 32 : Procedure to enable or disable and adjust Low Volt Equalize.