Chapter 5 _______________________________________________________________ Diagnostics
VAISALA_______________________________________________________________________ 83
The following sections list some of these event messages and give 
instructions for solving problems indicated by these messages. 
Note that you may need to use other AviMet maintenance applications, for 
example, IO Terminal, to solve the problems. For more information on the 
other maintenance applications, see the appropriate chapters in this 
manual. 
ABNORMAL SERVER STATUS, MISSING 
ROA SERVER OR NETWORK PROBLEM 
DETECTED BY SERVER X
This message indicates one of the following:
- Remote Object Server service is not running in the CDU: the Server 
status of the CDU is "Missing". 
- The server status of the CDU in the System Status panel is "Starting", 
"Manual Active", or "Manual Standby". 
- In duplicated systems both CDUs have the same status.
- There is a network problem (LAN problem). 
In the Diagnostics application, do the following to troubleshoot the 
situation:
1. Check the System status panel Server status column. If the Server 
status is "Missing", restart the Remote Object Server service. 
2. If the Server status is "Starting", wait for the system to start.
3. If the status is "Manual Active" or "Manual Standby", check that the 
manual change of the CDU status is still valid. If not, return the CDU 
to normal status.
4. If both CDUs have the same status, check the network connection (see 
section Checking Network Connection on page 87), or restart the 
system.