Vertiv™ NetSure™ 5100 Series -48 VDC Power System Installation Manual
Proprietary and Confidential © 2023 Vertiv Group Corp.
4
3 Installing the System
3.1 General Requirements
This product is intended only for installation in a restricted access location on or above a non-combustible surface.
This product must be located in a controlled environment with access to crafts persons only.
This product is intended for installation in network telecommunication facilities (CO, vault, hut, or other environmentally
controlled electronic equipment enclosure).
This product is intended for connection to the common bonding network in a network telecommunication facility (CO, vault,
hut, or other environmentally controlled electronic equipment enclosure).
The DC return connection to this system can remain isolated from system frame and chassis (DC-I).
This system is suitable for installation as part of the Common Bonding Network (CBN).
The installer should be familiar with the installation requirements and techniques to be used in securing the relay rack to the
floor.
The installer should be familiar with the installation requirements and techniques to be used in securing the distribution
cabinet with module mounting assembly(s) to a relay rack or equipment rack.
Rectifier, solar converter, converter, inverter (if equipped with optional inverter system) and module mounting assembly(s)
ventilating openings must not be blocked and temperature of air entering rectifiers, solar converters, converters, and
inverters must not exceed rated operating ambient temperature range found in SAG582137100.
Clearance requirements are:
a) Recommended minimum aisle space clearance for the front of each bay is 2' 6".
b) Recommended minimum aisle space clearance for the rear of each bay is 2’ 0” for any of the following conditions:
1. Addition of a module mounting assembly in the field.
2. Making input connections to a field installed module mounting assembly.
3. Adding battery tray(s) in the field.
For all other conditions, required minimum spacing from the rear of the system to a wall or other solid structure must not be
less than four (4) inches and from the front of the system not less than two (2) inches. This will assure proper airflow
through the rectifier, solar converter, and converter modules.
NOTE!
Minimum spacing specified for ventilation may not permit replacement of certain components such as busbars or
module mounting assemblies.
Front door and top / rear covers must be removed in cabinet applications above +40 °C (+104 °F). See SAG582137100 for
temperature ratings.
3.2 Securing the Relay Rack to the Floor
All equipment ordered is factory mounted to the relay rack or shipping rails specified when ordered.
Secure the relay rack to the floor per site requirements. Refer to General Requirements” on page 4.
Ventilation Requirements
Refer to General Requirements” on page 4.

Table of Contents

Other manuals for Vertiv NetSure 5100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 5100 Series and is the answer not in the manual?

Vertiv NetSure 5100 Series Specifications

General IconGeneral
BrandVertiv
ModelNetSure 5100 Series
CategoryPower Supply
LanguageEnglish

Related product manuals