Vertiv™ NetSure™ 5100 Series -48 VDC Power System Installation Manual
Proprietary and Confidential © 2023 Vertiv Group Corp.
63
4.5 Switch Settings on the SM-DU (List 60 Hybrid Connection Cabinet)
The SM-DU is used in a List 60 Hybrid Connection Cabinet to monitor the internal circuit breaker shunts.
SM-DU uses three (3) 8-bit switches for parameter setting (S1, S2, and S3). Refer to Table 4.3 for switch settings. Refer to Figure 4.7
for switch locations.
Perform the following procedure to verify the factory settings. This procedure can also be used to make adjustments on a
replacement circuit card.
4.5.1 Procedure
1. Ensure S1, S2, and S3 are set per Table 4.3. Refer to Figure 4.7 for location.
Table 4.3 Switch Settings on the SM-DU (List 60 Hybrid Connection Cabinet) (cont’d on next page)
DIP Switch S1
Communication
Address
Shunt
Voltage
Shunt
Current
Description of Status
1
2
3
4
5
6
7
8
OFF
OFF
OFF
NA
Address 8#
OFF
OFF
ON
Address 1# (Note 1)
OFF
ON
OFF
Address 2#
OFF
ON
ON
Address 3#
ON
OFF
OFF
Address 4#
ON
OFF
ON
Address 5#
ON
ON
OFF
Address 6#
ON
ON
ON
Address 7#
NA
OFF
OFF
NA
Shunt Voltage: 75 mV (Note 1)
OFF
ON
Shunt Voltage: 25 mV
ON
OFF
Shunt Voltage: 50 mV
ON
ON
Shunt Voltage: 60 mV
NA
OFF
OFF
OFF
Shunt Current: 500 A (Note 1)
OFF
OFF
ON
Shunt Current: 100 A
OFF
ON
OFF
Shunt Current: 200 A
OFF
ON
ON
Shunt Current: 300 A
ON
OFF
OFF
Shunt Current: 400 A
ON
OFF
ON
Shunt Current: 1000 A
ON
ON
OFF
Shunt Current: 1500 A
ON
ON
ON
Shunt Current: 2000 A
Note 1: Setting for this system.

Table of Contents

Other manuals for Vertiv NetSure 5100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 5100 Series and is the answer not in the manual?

Vertiv NetSure 5100 Series Specifications

General IconGeneral
BrandVertiv
ModelNetSure 5100 Series
CategoryPower Supply
LanguageEnglish

Related product manuals