Vertiv™ NetSure™ 5100 Series -48 VDC Power System Installation Manual
Proprietary and Confidential © 2023 Vertiv Group Corp.
64
Table 4.3 Switch Settings on the SM-DU (List 60 Hybrid Connection Cabinet)
(cont’d from previous page, cont’d on next page)
DIP Switch S2
Shunt 1
Setting
Shunt 2
Setting
Shunt 3
Setting
Shunt 4
Setting
Description of Status
1
2
3
4
5
6
7
8
OFF
OFF
NA
Shunt 1 is Disabled
OFF
ON
Shunt 1 is Used for Battery
ON
OFF
Shunt 1 is Used for Load
ON
ON
Set via Software (Note 1)
NA
OFF
OFF
NA
Shunt 2 is Disabled
OFF
ON
Shunt 2 is Used for Battery
ON
OFF
Shunt 2 is Used for Load
ON
ON
Set via Software (Note 1)
NA
OFF
OFF
NA
Shunt 3 is Disabled
OFF
ON
Shunt 3 is Used for Battery
ON
OFF
Shunt 3 is Used for Load
ON
ON
Set via Software (Note 1)
NA
OFF
OFF
Shunt 4 is Disabled
OFF
ON
Shunt 4 is Used for Battery
ON
OFF
Shunt 4 is Used for Load
ON
ON
Set via Software (Note 1)
Note 1: Setting for this system.

Table of Contents

Other manuals for Vertiv NetSure 5100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 5100 Series and is the answer not in the manual?

Vertiv NetSure 5100 Series Specifications

General IconGeneral
BrandVertiv
ModelNetSure 5100 Series
CategoryPower Supply
LanguageEnglish

Related product manuals