Vertiv™ NetSure™ 5100 Series -48 VDC Power System Installation Manual
Proprietary and Confidential © 2023 Vertiv Group Corp.
65
Table 4.3 Switch Settings on the SM-DU (List 60 Hybrid Connection Cabinet) (cont’d from previous page)
DIP Switch S3
Set via Software
Contactor Type
Safe Mode
Dry Contact
Description of Status
1
2
3
4
Off
NA
Shunt parameter is set through DIP switch.
On Shunt parameter is set via software.
(Note 1)
NA
Off
NA
Bi-Stable Contactor
(Note 1)
On Mono-Stable Contactor
NA
Off
NA
LVD / reconnection is disabled upon communication
failure.
(Note 1)
On
LVD / reconnection is enabled upon communication
failure.
NA
On LVD2 is a Dry Contact
Off LVD2
(Note 1)
DIP Switch S3
Shunt 5 Setting
Reserved
Calibration
Mode
Description
of Status
5
6
7
8
Off Off
NA
Shunt 5 is Disabled
Off On Shunt 5 is Used for Battery
(Note 1)
On Off Shunt 5 is Used for Load
On On Shunt 5 is Set via Software
NA
Off Operation Mode
(Note 1)
On Calibration Mode
Note 1: Setting for this system.

Table of Contents

Other manuals for Vertiv NetSure 5100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 5100 Series and is the answer not in the manual?

Vertiv NetSure 5100 Series Specifications

General IconGeneral
BrandVertiv
ModelNetSure 5100 Series
CategoryPower Supply
LanguageEnglish

Related product manuals