Vertiv™ NetSure™ 5100 Series -48 VDC Power System Installation Manual
Proprietary and Confidential © 2023 Vertiv Group Corp.
72
NOTE!
For systems with List 46 and -48 VDC to +24 VDC converters or -48 VDC to -58 VDC converters are being used (List
26 two row distribution panel or List 27 single row distribution panel) in the plant, the following module restrictions apply for
factory installed shelves 2 through 5:
o Rectifiers can be in any or all six (6) positions if three (3) AC inputs provided.
o +24V or -58V converters can be in the right three (3) positions (positions 4, 5 and 6).
o Rectifiers can be in any position which has AC power that is not taken up with a converter.
o One (1) Solar converter can be installed in the shelf, position 1 or 2.
o Three (3) solar converters can be installed in the shelf, positions 1 or 2, positions 3 or 4 and positions 5 or 6 if the -48V
to +24V or -48V to -58V bus bar is not installed to the shelf above.