EasyManua.ls Logo

Woodward GCP-30 Series - Page 67

Woodward GCP-30 Series
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 37278B GCP-30 Series - Genset Control
© Woodward Page 67/174
Open Breaker
Open GCB
The GCB will be opened both when the relay "Command: GCB close" de-energizes (only if "continuous pulse"
has been configured; Parameter 130), and relay "Command: GCB open" is energized. The GCB will be opened
under t
he following circumstances:
If a mains failure is detected and the mains decoupling is configured to the GCB (Parameter 159 or Para-
m
eter 160 depending on control unit)
In the operation mode STOP
If a class F2 or F3 alarm is present
Upon pressing the push-button "GCB OFF" or [GCP-32] "MCB ON" (depending on the breaker logic which
has been configured) in operation mode MANUAL
Upon pressing the push-button "STOP" in operation mode MANUAL
Upon pressing the push-button "GCB OFF" or [GCP-32] "MCB ON" (depending on the breaker logic which
has been configured) in operation mode LOAD TEST
In the event of an automatic stopping in the operation mode AUTOMATIC
[GCP-32] following the "CLOSED TRANSIT." (
make-before-break/overlap synchronization) of the MCB
[GCP-32] before the MCB is closed to the dead busbar in the case of the breaker logic "OPEN TRANSIT."
(break-before-make/changeover)
In critical mode/sprinkler operation, provided that no emergency power operation is present
[GCP-32] following the "INTERCHANGE" (mains interchange (import/export) real power control) of the
MCB
Open MCB [GCP-32]
The MCB will be opened via closing the relay "Command: MCB open" (configuration of "continuous pulse" is
not possible for the MCB). The MCB will be opened under the following circumstances:
If a mains monitoring triggers and the mains decoupling is configured to EXT (Parameter 160)
If emergency power (AMF) is enabled (mains failure)
following the "CLOSED TRANSIT." (
make-before-break/overlap synchronization) of the GCB
Before the GCB is closed to the dead busbar in the case of the breaker logic "OPEN TRANSIT." (break-
before-make/changeover)
Upon pressing the push-button "MCB OFF" or "GCB ON" (depending on the breaker logic which has been
configured) in operation mode MANUAL
Upon pressing the push-button "MCB OFF" or "GCB ON" (depending on the breaker logic which has been
configured) in operation mode LOAD TEST
Following the soft loading (interchange synchronization) of the MCB

Table of Contents

Other manuals for Woodward GCP-30 Series

Related product manuals