9Alarm
DX100 9.4 Alarm Message List
9-16
Connection failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
Servo control board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
Main CPU board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
101 COMMUNICATION
ERROR (servo#2)
1 The error was detected during the
check of the serial communication
watchdog data.
Counter value received from
Servo control board is invalid.
Setting error (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
Connection failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
Servo control board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
Converter unit failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
Main CPU board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
2 The error was detected during the
check of the number of the serial
communications.
Counter value received from
Servo control board is OFF by
one cycle.
Setting error (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
Connection failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
Servo control board failure (1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the controller. Save the CMOS.BIN before
replacement to be safe.
Alarm
Number
Alarm Name
Sub
Code
Meaning Cause Remedy