Parameter List
3
3.22 Parameters Changed by E5-01 [PM Motor Code Selection]
YASKAWA TOEPYAIGA5001A GA500 DRIVE MAINTENANCE & TROUBLESHOOTING 211
No. Name Unit Motor Code (setting value of E5-01)
E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5
E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6
L3-24
*1
Motor Accel Time @ Rated
Torque
s 0.084 0.096 0.085 0.080 0.122 0.108
n5-02
Motor Inertia Acceleration
Time
s 0.084 0.096 0.085 0.080 0.122 0.108
n8-49 Heavy Load Id Current % -12.2 -15.5 -15.1 -16.0 -15.7 -11.5
*1 The default setting changes when the setting for o2-04 [Drive Model Selection] changes.
Table 3.17 SSR1 Series Motor Code Setting for Specification of 200 V at 1150 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code Selection - 1402 1403 1405 1406 1408 140A
Voltage Class V 200 200 200 200 200 200
Capacity kW 0.4 0.75 1.5 2.2 3.7 5.5
Motor Rotation Speed min
-1
1150 1150 1150 1150 1150 1150
E5-02 PM Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5
E5-03
PM Motor Rated Current
(FLA)
A 1.88 3.02 6.00 8.85 14.27 20.21
E5-04 PM Motor Pole Count - 6 6 6 6 6 6
E5-05
PM Motor Resistance (ohms/
phase)
Ω 4.832 2.704 1.114 0.511 0.412 0.303
E5-06
PM d-axis Inductance (mH/
phase)
mH 48.68 32.31 19.22 12.15 7.94 11.13
E5-07
PM q-axis Inductance (mH/
phase)
mH 63.21 40.24 24.38 15.35 11.86 14.06
E5-09
PM Back-EMF Vpeak (mV/
(rad/s))
mVs/rad 320.4 327.1 364.4 344.4 357.5 430.8
E5-24
PM Back-EMF L-L Vrms
(mV/rpm)
mV/min
-1
0.0 0.0 0.0 0.0 0.0 0.0
E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5
E1-05 Maximum Output Voltage V 190.0 190.0 190.0 190.0 190.0 190.0
E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5
E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9 2.9 2.9
L3-24
*1
Motor Accel Time @ Rated
Torque
s 0.062 0.044 0.080 0.090 0.067 0.072
n5-02
Motor Inertia Acceleration
Time
s 0.062 0.044 0.080 0.090 0.067 0.072
n8-49 Heavy Load Id Current % -8.8 -9.9 -9.3 -10.0 -17.7 -12.3
*1 The default setting changes when the setting for o2-04 [Drive Model Selection] changes.
Table 3.18 SSR1 Series Motor Code Setting for Specification of 200 V at 1150 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code Selection - 140B 140D 140E 140F 1410
Voltage Class V 200 200 200 200 200
Capacity kW 7.5 11 15 18.5 22
Motor Rotation Speed min
-1
1150 1150 1150 1150 1150
E5-02 PM Motor Rated Power kW 7.5 11.0 15 18.50 22.00
E5-03 PM Motor Rated Current (FLA) A 26.67 39.9 55.6 63.5 74.4
E5-04 PM Motor Pole Count - 6 6 6 6 6
E5-05
PM Motor Resistance (ohms/
phase)
Ω 0.165 0.113 0.084 0.066 0.048