A.2 Parameter Table
334 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
1A Reverse Direction Closed: Drive is running in the reverse direction. O O O 168
1B
During Baseblock
(N.C.)
Open: Drive is in Baseblock condition. Output is disabled. O O O 168
1C Motor 2 Selection Closed: Motor 2 is selected by a digital input (H1- = 16) O O − 168
1E Restart Enabled Closed: An automatic restart is performed O O O 169
1F Overload Alarm OL1 Closed: OL1 is at 90% of its trip point or greater. O O O 169
20 OH Pre alarm Closed: Heatsink temperature exceeds the parameter L8-02 value. O O O 169
22
Mechanical Weakening
(N.O.)
Closed: Mechanical Weakening detected. O O O 169
30 During Torque Limit Closed: When the torque limit has been reached. − O − 169
37
During Frequency
Output
Closed: Frequency is output
Open: Operation stopped, Baseblock, DC Injection Braking, or
Initial Excitation is being performed.
OOO169
38 Drive Enable Closed: Multi-function input closes (H1- = 6A) O O O 170
39 Watt Hour Pulse Output
Output units are determined by H2-06, outputs 200 ms pulse for
each incremented kWh count.
OOO170
3C
LOCAL/REMOTE
Status
Closed: LOCAL
Open: REMOTE
OOO170
3D Speed Search Closed: Speed search is being executed. O O O 171
3E
PID Feedback Loss
Low
Closed: PID Feedback Loss Low.
PID feedback value is below the level set to b5-13 for longer than
the time set in b5-14.
OOO171
3F
PID Feedback Loss
High
Closed: PID Feedback Loss High.
PID feedback value exceeds the level set to b5-36 for longer than
the time set to b5-37.
OOO171
4A KEB Operation Closed: KEB is being performed. O O O 171
4B Short-Circuit Brake Closed: Short-Circuit Braking is active. −−O 171
4C During Fast-stop Closed: Fast-stop command is entered O O O 171