EasyManua.ls Logo

ABB ACS355 series - Process Controller PID1

ABB ACS355 series
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
152 Program features
Process controller PID1
PID1 has two separate sets of parameters (40 PROCESS PID SET 1, 41 PROCESS
PID SET 2). Selection between parameter sets 1 and 2 is defined by a parameter.
In most cases when there is only one transducer signal wired to the drive, only
parameter set 1 is needed. Two different parameter sets (1 and 2) are used, eg, when
the load of the motor changes considerably in time.
External/Trim controller PID2
PID2 (42 EXT / TRIM PID) can be used in two different ways:
External controller: Instead of using additional PID controller hardware, the user
can connect PID2 output through drive analog output or fieldbus controller to
control a field instrument like a damper or a valve.
Trim controller: PID2 can be used to trim or fine tune the reference of the drive.
See section Reference trimming on page 130.
Block diagrams
The figure below shows an application example: The controller adjusts the speed of a
pressure boost pump according to the measured pressure and the set pressure
reference.
ref
k
ti
td
i
dFiltT
errVInv
oh1
ol1
Speed
reference
%ref = 4010
.
.
.
AC T PA R FU NC DR IVE
E NT ER
LO C
RE M
RE SET
RE F
A C S 6 0 0
0 . . . 1 0 b a r
4 . . . 2 0 m A
3
3
2
Drive
PID control block diagramExample:
Pressure boost pump
4001
4002
4003
4004
4005
PIDmin
PIDmax
4014
4021
AI1
AI2
IMOT
%ref
Actual values
PID
Switch
9904 = 0
Frequency
reference

Table of Contents

Other manuals for ABB ACS355 series

Related product manuals