198 Actual signals and parameters
DI3U,4D See parameter 110 3 REF1 SELECT.6
COMM See parameter 1103 REF1 SELECT.8
COMM+AI1 See parameter 1103 REF1 SELECT.9
COMM*AI1 See parameter 1103 REF1 SELECT.10
DI3U,4D(RNC) See parameter 110 3 REF1 SELECT.11
DI3U,4D(NC) See parameter 1103 REF1 SELECT.12
AI1+AI2 See parameter 1103 REF1 SELECT.14
AI1*AI2 See parameter 1103 REF1 SELECT.15
AI1-AI2 See parameter 1103 REF1 SELECT.16
AI1/AI2 See parameter 1103 REF1 SELECT.17
PID1OUT PID controller 1 output. See parameter groups
40 PROCESS PID SET 1 and 41 PROCESS PID SET 2.
19
KEYPAD(RNC) See parameter 1103 REF1 SELECT.20
KEYPAD(NC) See parameter 1103 REF1 SELECT.21
DI4U,5D See parameter 1103 REF1 SELECT.30
DI4U,5D(NC) See parameter 1103 REF1 SELECT.31
FREQ INPUT See parameter 1103 REF1 SELECT.32
SEQ PROG See parameter 1103 REF1 SELECT.33
AI1+SEQ
PROG
See parameter 1103 REF1 SELECT.34
AI2+SEQ
PROG
See parameter 1103
REF1 SELECT.35
1107 REF2 MIN Defines the minimum value for external reference REF2.
Corresponds to the minimum setting of the used source
signal.
0.0%
0.0…100.0% Value as a percentage of the maximum frequency /
maximum speed / nominal torque. See the example for
parameter 1104 REF1 MIN for correspondence to the
source signal limits.
1 = 0.1%
1108 REF2 MA Defines the maximum value for external reference REF2.
Corresponds to the maximum setting of the used source
signal.
100.0%
0.0…100.0% Value as a percentage of the maximum frequency /
maximum speed / nominal torque. See the example for
parameter 1104 REF1 MIN for correspondence to the
source signal limits.
1 = 0.1%
1109 ODVA HZ REF
SEL
Decimal point location for ODVA frequency reference values
if parameter 1103 REF1 SELECT = ODVA HZ REF
1
SCALE 1 ODVA profile Hz reference 500 equals 50.0 Hz in EXT1. 1
SCALE 2 ODVA profile Hz reference 5000 equals 50.00 Hz in EXT1. 2
All parameters
No. Name/Value Description Def/FbEq

Table of Contents