222 Parameters
14.86 AO2 actual value (Visible when 14.01 Module 1 type = FA I O -01 )
Displays the value of AO2 in mA.
This parameter is read-only.
-
0.000 … 22.000 mA Value of AO2. 1000 = 1 mA
14.87 AO2 source (Visible when 14.01 Module 1 type = FA IO -01 )
Selects a signal to be connected to analog output AO2.
Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor.
For the selections, see parameter 14.77 AO1 source.
Zero
14.88 AO2 force data (Visible when 14.01 Module 1 type = FAIO -0 1 )
Forced value that can be used instead of the selected output
signal. See parameter 14.71 AO force selection.
0.000 mA
0.000 … 22.000 mA Forced value of analog output AO2. 1000 = 1 mA
14.89 AO2 filter time (Visible when 14.01 Module 1 type = FA IO-01 )
Defines the filtering time constant for analog output AO2. See
parameter 14.79 AO1 filter time.
0.100 s
0.000 … 30.000 s Filter time constant. 1000 = 1 s
14.90 AO2 source min (Visible when 14.01 Module 1 type = FA IO-01 )
Defines the real value of the signal (selected by parameter
14.87 AO2 source) that corresponds to the minimum AO2
output value (defined by parameter 14.92 AO2 out at AO2 src
min).
0.0
-32768.0 …
32767.0
Real signal value corresponding to minimum AO2 output
value.
1 = 1