Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1000 = 1 mA / 1000 =
1 mA
Minimum AO1 output value.0.000 ... 22.000 mA
0.000 mA / real32(Visible when 14.1 Module 1 type = FAIO-01)
Defines the minimum output value for analog output
AO1.
See also drawing at parameter 14.80 AO1 source min.
AO1 out at AO1 src
min
14.82
1000 = 1 mA / 1000 =
1 mA
Minimum AO1 output value.0.000 ... 20.000 mA
10.000 mA / real32(Visible when 14.1 Module 1 type = FIO-11)
Defines the maximum output value for analog output
AO1.
See also drawing at parameter 14.80 AO1 source min.
AO1 out at AO1 src
max
14.83
1000 = 1 mA / 1000 =
1 mA
Maximum AO1 output value.0.000 ... 22.000 mA
10.000 mA / real32(Visible when 14.1 Module 1 type = FAIO-01)
Defines the maximum output value for analog output
AO1.
See also drawing at parameter 14.80 AO1 source min.
AO1 out at AO1 src
max
14.83
1000 = 1 mA / 1000 =
1 mA
Maximum AO1 output value.0.000 ... 20.000 mA
- / real32(Visible when 14.1 Module 1 type = FAIO-01)
Displays the value of AO2 in mA.
This parameter is read-only.
AO2 actual value14.86
1000 = 1 mA / 1000 =
1 mA
Value of AO2.0.000 ... 22.000 mA
Zero / uint32(Visible when 14.1 Module 1 type = FAIO-01)
Selects a signal to be connected to analog output AO2.
Alternatively, sets the output to excitation mode to
feed a constant current to a temperature sensor.
For the selections, see parameter 14.77 AO1 source.
AO2 source14.87
0.000 mA / real32(Visible when 14.1 Module 1 type = FAIO-01)
Forced value that can be used instead of the selected
output signal. See parameter 14.71 AO force selection.
AO2 force data14.88
1000 = 1 mA / 1000 =
1 mA
Forced value of analog output AO2.0.000 ... 20.000 mA
0.100 s / real32(Visible when 14.1 Module 1 type = FAIO-01)
Defines the filtering time constant for analog output
AO2. See parameter 14.79 AO1 filter time.
AO2 filter time14.89
1000 = 1 s / 1000 = 1
s
Filter time constant.0.000 ... 30.000 s
Parameters 261