Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
4The sources of the start and stop commands are
selected by parameters 20.8 Ext2 in1 source and 20.9
Ext2 in2 source.
The state transitions of the source bits are interpreted
as follows:
CommandState of source 2
(20.9)
State of source 1
(20.8)
Start10?1
Stop0Any
Note: The start signal is always edge-triggered with
this setting regardless of parameter 20.7 Ext2 start
trigger type.
In1P Start; In2 Stop
5The sources of the start and stop commands are
selected by parameters 20.8 Ext2 in1 source and 20.9
Ext2 in2 source.
The source selected by 20.10 Ext2 in3 source
determines the direction. The state transitions of the
source bits are interpreted as follows:
CommandState of
source 3
(20.10)
State of
source 2
(20.9)
State of
source 1
(20.8)
Start forward010?1
Start reverse110?1
StopAny0Any
Note: The start signal is always edge-triggered with
this setting regardless of parameter 20.7 Ext2 start
trigger type.
In1P Start; In2 Stop;
In3 Dir
6The sources of the start and stop commands are
selected by parameters 20.8 Ext2 in1 source, 20.9 Ext2
in2 source and 20.10 Ext2 in3 source. The state
transitions of the source bits are interpreted as follows:
CommandState of
source 3
(20.10)
State of
source 2
(20.9)
State of
source 1
(20.8)
Start forward1Any0?1
Start reverse10?1Any
Stop0AnyAny
Note: The start signal is always edge-triggered with
this setting regardless of parameter 20.7 Ext2 start
trigger type.
In1P Start fwd; In2P
Start rev; In3 Stop
11The start and stop commands are taken from the
control panel.
Control panel
Parameters 283