Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Not selected / uint32Selects the source for a jog enable signal.
(The sources for jogging activation signals are selected
by parameters 20.26 Jogging 1 start source and 20.27
Jogging 2 start source.)
1 = Jogging is enabled.
0 = Jogging is disabled.
Note: Jogging can be enabled only when no start
command from an external control location is active.
On the other hand, if jogging is already enabled, the
drive cannot be started from an external control
location (apart from inching commands through
fieldbus).
See section Jogging (page 99).
Jogging enable20.25
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO1 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
Not selected / uint32If enabled by parameter 20.25 Jogging enable, selects
the source for the activation of jogging function 1.
(Jogging function 1 can also be activated through
fieldbus regardless of parameter 20.25.)
1 = Jogging 1 active.
Note: If both jogging 1 and 2 are activated, the one that
was activated first has priority.
Jogging 1 start
source
20.26
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 02).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
288 Parameters