Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
2The drive trips on fault 2330 Earth leakage.Fault
Fault/Fault / uint16Selects which indications are given when both Safe
torque off (STO) signals are switched off or lost. The
indications also depend on whether the drive is running
or stopped when this occurs.
The tables at each selection below show the indications
generated with that particular setting.
Note:
This parameter does not affect the operation of
the STO function itself. The STO function will
operate regardless of the setting of this
parameter: a running drive will stop upon removal
of one or both STO signals, and will not start until
both STO signals are restored and all faults reset.
The loss of only one STO signal always generates
a fault as it is interpreted as a malfunction.
This parameter cannot be changed while the drive
is running.
For more information on the STO, see the Hardware
manual of the drive.
STO indication
run/stop
31.22
0
Indication (running
or stopped)
Inputs
IN2IN1
Fault 5091 Safe
torque off
00
Faults 5091 Safe
torque off and FA81
Safe torque off 1
loss
10
Faults 5091 Safe
torque off and FA82
Safe torque off 2
loss
01
(Normal operation)11
Fault/Fault
370 Parameters