Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
150.00; 180.00 rpm
(95.20 b0) rpm /
real32
Stall speed limit in rpm. See parameter 31.24 Stall
function.
Stall speed limit31.26
- / -Stall speed limit. For scaling, see parameter 46.1.0.00 ... 10000.00
rpm
15.00; 18.00 Hz (95.20
b0) Hz / real32
Stall frequency limit. See parameter 31.24 Stall function.
Note: Setting the limit below 10 Hz is not
recommended.
Stall frequency limit31.27
- / -Stall frequency limit. For scaling, see parameter 46.2.0.00 ... 500.00 Hz
20 s / real32Stall time. See parameter 31.24 Stall function.Stall time31.28
1 = 1 s / 1 = 1 sStall time.0...3600 s
500.00 rpm / real32Defines, together with 30.11 Minimum speed and 30.12
Maximum speed, the maximum allowed speed of the
motor (overspeed protection). If 90.1 Motor speed for
control or the estimated speed exceeds the speed limit
defined by parameter 30.11 or 30.12 by more than the
value of this parameter, the drive trips on the 7310
Overspeed.
Example: If the maximum speed is 1420 rpm and speed
trip margin is 300 rpm, the drive trips at 1720 rpm.
Speed
(
90.01
)
Time
Overspeed trip level
(
31.30
)
(
30.12
)
(
30.11
)
(
31.30
)
Overspeed trip level
0
Overspeed trip
margin
31.30
- / -Overspeed trip margin. For scaling, see parameter 46.1.0.00 ... 10000.00
rpm