Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
4
Indication (running
or stopped)
Inputs
IN2IN1
Event B5A0 STO
event
00
Event B5A0 STO
event and fault
FA81 Safe torque
off 1 loss
10
Event B5A0 STO
event and fault
FA82 Safe torque
off 2 loss
01
(Normal operation)11
Event/Event
5
Indication (running
or stopped)
Inputs
IN2IN1
None00
Fault FA81 Safe
torque off 1 loss
10
Fault FA82 Safe
torque off 2 loss
01
(Normal operation)11
No indication/No
indication
Fault; No action
(95.20 b15) / uint16
Selects how the drive reacts to incorrect input power
and motor cable connection (i.e. input power cable is
connected to drive motor connection).
Note: The protection must be disabled with
drive/inverter hardware supplied from a common DC
bus.
Wiring or earth fault31.23
0No action taken (protection disabled).No action
1The drive trips on fault 3181 Wiring or earth fault.Fault
Fault / uint16Selects how the drive reacts to a motor stall condition.
A stall condition is defined as follows:
The drive exceeds the stall current limit (31.25 Stall
current limit), and
the output frequency is below the level set by
parameter 31.27 Stall frequency limit or the motor
speed is below the level set by parameter 31.26
Stall speed limit, and
the conditions above have been true longer than
the time set by parameter 31.28 Stall time.
Stall function31.24
0None (stall supervision disabled).No action
1The drive generates an A780 Motor stall.Warning
2The drive trips on fault 7121 Motor stall.Fault
200.0 % / real32Stall current limit in percent of the nominal current of
the motor. See parameter 31.24 Stall function.
Stall current limit31.25
10 = 1 % / 10 = 1 %Stall current limit.0.0 ... 1600.0 %
372 Parameters