Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
12Parameter 74.1 ESP control word (page 519), bit 10
status controls enable/disable status of the function.
ESP CW bit 10
See Terms and abbreviations (page 169).Other [bit]
10.00 Hz / real32Defines frequency point 1 in the custom user U/F curve.Frequency point 180.11
10 = 1 Hz / 100 = 1 HzFrequency point 1.2.00 ... 600.00 Hz
20.00 Hz / real32Defines frequency point 2 in the custom user U/F curve.Frequency point 280.12
10 = 1 Hz / 100 = 1 HzFrequency point 2.2.00 ... 600.00 Hz
30.00 Hz / real32Defines frequency point 3 in the custom user U/F curve.Frequency point 380.13
10 = 1 Hz / 100 = 1 HzFrequency point 3.2.00 ... 600.00 Hz
40.00 Hz / real32Defines frequency point 4 in the custom user U/F curve.Frequency point 480.14
10 = 1 Hz / 100 = 1 HzFrequency point 4.2.00 ... 600.00 Hz
45.00 Hz / real32Defines frequency point 5 in the custom user U/F curve.Frequency point 580.15
10 = 1 Hz / 100 = 1 HzFrequency point 5.2.00 ... 600.00 Hz
50.00 Hz / real32Defines frequency point 5 in the custom user U/F curve.Frequency point 680.16
10 = 1 Hz / 100 = 1 HzFrequency point 6.2.00 ... 600.00 Hz
55.00 Hz / real32Defines frequency point 5 in the custom user U/F curve.Frequency point 780.17
10 = 1 Hz / 100 = 1 HzFrequency point 7.2.00 ... 600.00 Hz
60.00 Hz / real32Defines frequency point 8 in the custom user U/F curve.Frequency point 880.18
10 = 1 Hz / 100 = 1 HzFrequency point 8.2.00 ... 600.00 Hz
Voltage / unit32Selects the input mode for additive values in the
custom U/F curve.
Voltage correction
style
80.20
0Additive value type for U/F curve selected as voltage.Voltage
1Additive value type for U/F curve selected as flux.Flux
0.00% / real32Defines additive point 1 in the custom user U/F curve.
The additive value type can be voltage of flux. This can
be selected in the parameter 80.20 Voltage correction
style.
Additive value 180.21
10 = 1% / 100 = 1%Additive value 1.-100.00 ... 100.00%
0.00% / real32Defines additive point 2 in the custom user U/F curve.Additive value 280.22
10 = 1% / 100 = 1%Additive value 2.-100.00 ... 100.00%
0.00% / real32Defines additive point 3 in the custom user U/F curve.Additive value 380.23
10 = 1% / 100 = 1%Additive value 3.-100.00 ... 100.00%
0.00% / real32Defines additive point 4 in the custom user U/F curve.Additive value 480.24
10 = 1% / 100 = 1%Additive value 4.-100.00 ... 100.00%
0.00% / real32Defines additive point 5 in the custom user U/F curve.Additive value 580.25
Parameters 547