Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / -Number of inverter modules available.0...65535
- / uint16
(Only visible with a BCU control unit)
Shows which of the parallel-connected inverter modules
have been detected by the control program.
Note: This parameter is read-only.
Connected modules95.14
Module 1 has been detected.b0
Module 2 has been detected.b1
Module 3 has been detected.b2
Module 4 has been detected.b3
Module 5 has been detected.b4
Module 6 has been detected.b5
Module 7 has been detected.b6
Module 8 has been detected.b7
Module 9 has been detected.b8
Module 10 has been detected.b9
Module 11 has been detected.b10
Module 12 has been detected.b11
Reservedb12…15
1 = 10000h…FFFFh
- / uint16Contains hardware-related settings that can be enabled
and disabled by toggling the specific bits.
Note: The installation of the hardware specified by this
parameter may require derating of drive output, or
impose other limitations. Refer to the hardware manual
of the drive.
Note: This parameter cannot be changed while the
drive is running.
Special HW settings95.15
1 = The driven motor is an Ex motor provided by ABB
for potentially explosive atmospheres. This sets the
required minimum switching frequency for ABB Ex
motors.
Note: For non-ABB Ex motors, contact your local ABB
representative.
EX motorb0
1 = An ABB sine filter is connected to the output of the
drive/inverter.
ABB sine filterb1
1 = Minimum switching frequency limit adaptation to
output frequency active. This setting improves control
performance at high output frequencies (typically
above 120 Hz.
High speed modeb2
596 Parameters