Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = A custom sine filter is connected to the output of
the drive/inverter. See also parameters 97.1, 97.2, 99.18,
99.19.
Custom sine filterb3
Reservedb4…15
1 = 10000h…FFFFh
Off / uint32
(Only visible with a BCU control unit)
Enables/disables router mode of the BCU control unit.
When router mode is active, the PSL2 channels
connected to another BCU (ie. those selected by 95.17
Router channel config) are routed to the power units
(converter modules) connected to this BCU.
See section Router mode for BCU control unit (page 146).
Note: This parameter cannot be changed while the
drive is running.
Router mode95.16
0Router mode inactive.Off
1Router mode active.On
See Terms and abbreviations (page 169).Other [bit]
- / uint16
(Only visible with a BCU control unit)
Selects which PSL2 channels on the BCU control unit
are connected to another BCU and routed to a local
power unit.
Note: The local power units are to be connected to
successive channels starting from CH1. The other BCU
is then connected to one or more successive channels
starting from the first free channel.
Note: The lowest channel selected in this parameter is
routed to the local power unit with the lowest number,
etc.
Note: There must be at least as many local power
modules as there are routed channels.
Note: This parameter cannot be changed while the
drive is running.
See section Router mode for BCU control unit (page 146).
Router channel
config
95.17
0b0
1 = Channel CH2 is routed to the local power unit (which
is connected to CH1)
b1
1 = Channel CH3 is routed to the local power unit (which
is connected to CH1)
b2
1 = Channel CH4 is routed to a local power unitb3
1 = Channel CH5 is routed to a local power unitb4
1 = Channel CH6 is routed to a local power unitb5
1 = Channel CH7 is routed to a local power unitb6
1 = Channel CH8 is routed to a local power unitb7