EasyManua.ls Logo

ABB ACS880 - Page 665

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
What to doCause
Event name /
Aux. code
Code
(hex)
Check the communication between
drive and control panel or PC. Retry.
Parameter load or save timeout
caused by communication break
between drive and control panel, or
control panel and PC tool.
Backup/Restore
Timeout
6591
Check PLC programming.The drive does not have a functionality
requested by PLC, or requested
functionality has not been activated.
FBA A
parameter
conflict
65A1
Check settings of parameter groups
50 Fieldbus adapter (FBA) and 51 FBA
A settings.
Check PLC programming.The drive does not have a functionality
requested by PLC, or requested
functionality has not been activated.
FBA B
parameter
conflict
65A2
Check settings of parameter groups
50 Fieldbus adapter (FBA) and 54 FBA
B settings.
See A6DA Reference source
parametrization (page 678).
A reference source is simultaneously
connected to multiple parameters
with different units.
Reference
source
parametrization
65B1
Check the status of the fieldbus
master (online/offline/error etc.).
Communication break in embedded
fieldbus (EFB) communication.
EFB
communication
loss
6681
Check cable connections to the XD2D
connector on the control unit.
Contact your local ABB representative.Embedded fieldbus (EFB)
configuration file could not be read.
EFB
configuration
file
6682
Check the settings in parameter group
58 Embedded fieldbus.
Embedded fieldbus (EFB) parameter
settings inconsistent or not
compatible with selected protocol.
EFB invalid
parameterization
6683
Contact your local ABB representative.EFB load fault6684
Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Version mismatch between EFB
protocol firmware and drive
firmware.
Reset the fault. Contact your local ABB
representative if the fault persists.
Internal fault.Text data
overflow
6881
Reset the fault. Contact your local ABB
representative if the fault persists.
Internal fault.Text 32-bit
table overflow
6882
Reset the fault. Contact your local ABB
representative if the fault persists.
Internal fault.Text 64-bit
table overflow
6883
Reset the fault. Contact your local ABB
representative if the fault persists.
Internal fault.Text file
overflow
6885
See A798 Encoder option comm
loss (page 681).
Communication between drive and an
option module is lost.
Option
module comm
loss
7080
Check PC tool or control panel
connection.
Control panel (or PC tool) has stopped
communicating.
Control panel
loss
7081
Check control panel connector.
Disconnect and reconnect the control
panel.
Fault tracing 665

Table of Contents

Other manuals for ABB ACS880

Related product manuals