What to doCause
Event name /
Aux. code
Code
(hex)
Check settings of parameter 99.12
Motor nominal torque, and the
torque limits in group 30 Limits.
Maximum torque limit too low.0003
Make sure that the maximum torque
limit in force is greater than 100%.
Contact your local ABB
representative.
Current measurement calibration
did not finish within reasonable
time.
0004
Contact your local ABB
representative.
Internal error.0005…0008
Contact your local ABB
representative.
(Asynchronous motors only)
Acceleration did not finish within
reasonable time.
0009
Contact your local ABB
representative.
(Asynchronous motors only)
Deceleration did not finish within
reasonable time.
000A
Contact your local ABB
representative.
(Asynchronous motors only) Speed
dropped to zero during ID run.
000B
Contact your local ABB
representative.
(Permanent magnet motors only)
First acceleration did not finish
within reasonable time.
000C
Contact your local ABB
representative.
(Permanent magnet motors only)
Second acceleration did not finish
within reasonable time.
000D
Contact your local ABB
representative.
Internal error.000E…0010
Try to perform ID run again.(SynRM only) Rotor orientation not
correct during the pulse test.
0011
Contact your local ABB
representative.
Check that nominal power is as
advised in Advanced Standstill ID
run description.
Not possible to perform Advanced
Standstill ID run.
0012
Contact your local ABB
representative.
Check name plate data.(Asynchronous motors only) Error
in motor data.
0013
Contact your local ABB
representative.
Contact your local ABB
representative.
Acceleration did not finish within
reasonable time during Autophasing
ID run.
0014
Contact your local ABB
representative.
Advanced standstill failure.0015
Check the auxiliary code. Add 2 to the
code to find out the node address of
the faulted drive.
A follower drive has tripped.FollowerFF7E
Correct the fault in the follower drive.
Check the fault information provided
by the PLC.
A fault trip command has been
received through fieldbus adapter A.
FB A force tripFF81
Check the fault information provided
by the PLC.
A fault trip command has been
received through fieldbus adapter B.
FB B force tripFF82
Fault tracing 695