Bit Name Val. Information
0 START ACT 1 Drive start command is active.
0 Drive start command is inactive.
1 STOP ACT 1 Drive stop command is active.
0 Drive stop command is inactive.
2 READY RELAY 1 Ready to function: run enable signal on, no fault, emergency stop
signal off, no ID run inhibition. Connected by default to DIO1 by par.
12.04 DIO1 OUT PTR. (Can be freely connected anywhere.)
0 Not ready to function
3 MODULATING 1 Modulating: IGBTs are controlled, i.e. the drive is RUNNING.
0 No modulation: IGBTs are not controlled.
4 REF RUNNING 1 Normal operation is enabled. Running. Drive follows the given
reference.
0 Normal operation is disabled, Drive is not following the given
reference (e.g. in magnetisation phase drive is modulating).
5 JOGGING 1 Jogging function 1 or 2 is active.
0 Jogging function is inactive.
6 OFF1 1 Emergency stop OFF1 is active.
0 Emergency stop OFF1 is inactive.
7 START INH
MASK
1 Maskable (by par. 10.12 START INHIBIT) start inhibit is active.
0 No start inhibit (maskable)
8 START INH
NOMASK
1 Non-maskable start inhibit is active.
0 No start inhibit (non-maskable)
9 CHRG REL
CLOSED
1 Charging relay is closed.
0 Charging relay is open.
10 STO ACT 1 Safe Torque Off function is active. See parameter 46.07 STO DIAG-
NOSTIC.
0 Safe Torque Off function is inactive.
11 Reserved
12 RAMP IN 0 1 Ramp Function Generator input is forced to zero.
0 Normal operation
13 RAMP HOLD 1 Ramp Function Generator output is held.
0 Normal operation
14 RAMP OUT 0 1 Ramp Function Generator output is forced to zero.
0 Normal operation
15 Reserved