EasyManua.ls Logo

ABB ACSM1 - Page 93

ABB ACSM1
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters and firmware blocks
93
6.03 SPEED CTRL STAT FW block: DRIVE LOGIC (page 103)
Speed control status word.
6.05 LIMIT WORD 1 FW block: DRIVE LOGIC (page 103)
Limit word 1.
Bit Name Val. Information
0 SPEED ACT
NEG
1 Actual speed is negative.
1 ZERO SPEED 1 Actual speed has reached the zero speed limit (22.05 ZERO
SPEED LIMIT).
2 ABOVE LIMIT 1 Actual speed has exceeded the supervision limit (22.07 ABOVE
SPEED LIM).
3 AT SETPOINT 1 The difference between the actual speed and the unramped
speed reference is within the speed window (26.07 SPEED WIN-
DOW).
4 BAL ACTIVE 1 Speed controller output balancing is active (28.09 SPEEDCTRL
BAL EN).
5…15 Reserved
Bit Name Val. Information
0 TORQ LIM 1 Drive torque is being limited by the motor control (undervoltage
control, overvoltage control, current control, load angle control or
pull-out control), or by parameter 20.06 MAXIMUM TORQUE or
20.07 MINIMUM TORQUE.
1 SPD CTL TLIM
MIN
1 Speed controller output minimum torque limit is active. The limit is
defined by parameter 28.10 MIN TORQ SP CTRL.
2 SPD CTL TLIM
MAX
1 Speed controller output maximum torque limit is active. The limit
is defined by parameter 28.11 MAX TORQ SP CTRL.
3 TORQ REF MAX 1 Torque reference (3.09 TORQ REF1) maximum limit is active.
The limit is defined by parameter 32.04 MAXIMUM TORQ REF.
4 TORQ REF MIN 1 Torque reference (3.09 TORQ REF1) minimum limit is active. The
limit is defined by parameter 32.05 MINIMUM TORQ REF.
5 TLIM MAX
SPEED
1 Torque reference maximum value is limited by the rush control,
because of maximum speed limit 20.01 MAXIMUM SPEED.
6TLIM MIN
SPEED
1 Torque reference minimum value is limited by the rush control,
because of minimum speed limit 20.02 MINIMUM SPEED.
7…15 Reserved

Table of Contents