Figure 549: Logic diagram of auto-initiation sequence detection
Automatic initiation can be selected with the
Auto initiation Cnd
setting to be the
following:
Not allowed: no automatic initiation is allowed
When the synchronization fails, the automatic initiation is carried out when the
auto wait time elapses and the reclosing is prevented due to a failure during the
synchronism check
When the circuit breaker does not close, the automatic initiation is carried out
if the circuit breaker does not close within the wait close time after issuing the
reclose command
Both: the automatic initiation is allowed when synchronization fails or the circuit
breaker does not close.
The
Auto init
parameter defines which INIT_X lines are activated in the
auto-initiation. The default value for this parameter is "0", which means
that no auto-initiation is selected.
1MRS757644 H Control functions
620 series
Technical Manual
1031