3.1.12 HMI settings
Table 18: HMI settings
Parameter Values (Range) Unit Step Default Description
FB naming conven-
tion
1=IEC61850
2=IEC60617
3=IEC-ANSI
1=IEC61850 FB naming conven-
tion used in IED
Default view
1=Measurements
2=Main menu
3=SLD
1=Measurements LHMI default view
Backlight timeout 1...60 min 1 3 LHMI backlight
timeout
Web HMI mode
1=Active read only
2=Active
3=Disabled
3=Disabled Web HMI function-
ality
Web HMI timeout 1...60 min 1 3 Web HMI login
timeout
SLD symbol format
1=IEC
2=ANSI
1=IEC Single Line Dia-
gram symbol for-
mat
Autoscroll delay 0...30 s 1 0 Autoscroll delay
for Measurements
view
Setting visibility
1=Basic
2=Advanced
1=Basic Setting visibility for
HMI
3.1.13 IEC 60870-5-103 settings
Table 19: IEC 60870-5-103 settings
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
5=off Selects if this pro-
tocol instance is
enabled or disabled
Serial port
1=COM 1
2=COM 2
1=COM 1 COM port
Address 1...255 1 1 Unit address
Start delay 0...20 char 1 4 Start frame delay in
chars
End delay 0...20 char 1 4 End frame delay in
chars
DevFunType 0...255 1 9 Device Function
Type
UsrFunType 0...255 1 10 Function type for
User Class 2 Frame
UsrInfNo 0...255 1 230 Information Num-
ber for User Class2
Frame
Table continues on the next page
Basic functions 1MRS757644 H
58 620 series
Technical Manual