4.11.7 Settings
Table 733: MAPGAPC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value –10000.0...10000.0 0.1 0.0 Start value
Start value Add –100.0...100.0 0.1 0.0 Start value Add
Operate delay time 0...200000 ms 100 0 Operate delay time
Table 734: MAPGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operation mode
1=Over
2=Under
1=Over Operation mode
Table 735: MAPGAPC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 100 0 Reset delay time
Absolute hysteresis 0.01...100.00 0.01 0.10 Absolute hysteresis
for operation
4.11.8 Monitored data
Table 736: MAPGAPC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
MAPGAPC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.11.9 Technical data
Table 737: MAPGAPC Technical data
Characteristic
Value
Operation accuracy
±1.0 % of the set value or ±20 ms
4.12 Capacitor bank protection
Protection functions
1MRS757644 H
772 620 series
Technical Manual