10.3.9 Monitored data
Table 1048: PHQVVR Monitored data
Name Type Values (Range) Unit Description
ST_A BOOLEAN
0=False
1=True
Start Phase A (Voltage
Variation Event in pro-
gress)
ST_B BOOLEAN
0=False
1=True
Start Phase B (Voltage
Variation Event in pro-
gress)
ST_C BOOLEAN
0=False
1=True
Start Phase C (Voltage
Variation Event in pro-
gress)
INSTSWELLCNT INT32 0...2147483647 Instantaneous swell op-
eration counter
MOMSWELLCNT INT32 0...2147483647 Momentary swell oper-
ation counter
TEMPSWELLCNT INT32 0...2147483647 Temporary swell opera-
tion counter
MAXDURSWELLCNT INT32 0...2147483647 Maximum duration
swell operation counter
INSTDIPCNT INT32 0...2147483647 Instantaneous dip oper-
ation counter
MOMDIPCNT INT32 0...2147483647 Momentary dip opera-
tion counter
TEMPDIPCNT INT32 0...2147483647 Temporary dip opera-
tion counter
MAXDURDIPCNT INT32 0...2147483647 Maximum duration dip
operation counter
MOMINTCNT INT32 0...2147483647 Momentary interrup-
tion operation counter
TEMPINTCNT INT32 0...2147483647 Temporary interruption
operation counter
SUSTINTCNT INT32 0...2147483647 Sustained interruption
operation counter
MAXDURINTCNT INT32 0...2147483647 Maximum duration in-
terruption operation
counter
PHQVVR Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Time Timestamp Time
Variation type Enum
0=No variation
1=Swell
2=Dip
3=Swell + dip
4=Interruption
5=Swell + Int
6=Dip + Int
7=Swell+dip+Int
Variation type
Variation Ph A FLOAT32 0.00...5.00 xUn Variation magnitude
Phase A
Var Ph A rec time Timestamp Variation magnitude
Phase A time stamp
Table continues on the next page
1MRS757644 H Power quality measurement functions
620 series
Technical Manual
1105