ABB Relion 620 Series - SMV Function Blocks; IEC 61850-9-2 LE Sampled Values Sending SMVSENDER

ABB Relion 620 Series
1224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 62: 2RTD/1mA monitored data
Name Type Values (Range) Unit Description
AI_DB1 FLOAT32 -10000.0...10000.
0
mA input, Con-
nectors 1-2, re-
ported value
AI_RANGE1 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
mA input, Con-
nectors 1-2,
range
AI_DB2 FLOAT32 -10000.0...10000.
0
RTD input, Con-
nectors 3-5, re-
ported value
AI_RANGE2 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Con-
nectors 3-5,
range
AI_DB3 FLOAT32 -10000.0...10000.
0
RTD input, Con-
nectors 6-8, re-
ported value
AI_RANGE3 Enum
0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Con-
nectors 6-8,
range
3.14 SMV function blocks
SMV function blocks are used in the process bus applications with the sending of
the sampled values of analog currents and voltages and with the receiving of the
sampled values of voltages.
3.14.1 IEC 61850-9-2 LE sampled values sending SMVSENDER
3.14.1.1 Functionality
The SMVSENDER function block is used for activating the SMV sending
functionality. It adds/removes the sampled value control block and the related data
set into/from the sending device's configuration. It has no input or output signals.
1MRS757644 H
Basic functions
620 series
Technical Manual
133

Table of Contents