Name Type Description
PROT_CRD BOOLEAN A signal for coordination between
the AR and the protection
UNSUC_RECL BOOLEAN Indicates an unsuccessful reclosing
sequence
AR_ON BOOLEAN Autoreclosing allowed
READY BOOLEAN Indicates that the AR is ready for
a new sequence, i.e. the CB_READY
input equals TRUE
ACTIVE BOOLEAN Reclosing sequence is in progress
9.4.8 Settings
Table 1008: DARREC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off/On
Reclosing opera-
tion
1=Off
2=External Ctl
3=On
1=Off Reclosing opera-
tion (Off, External
Ctl / On)
Close pulse time 10...10000 ms 10 200 CB close pulse time
Reclaim time 100...1800000 ms 100 10000 Reclaim time
Terminal priority
1=None
2=Low (follower)
3=High (master)
1=None Terminal priority
Synchronisation
set
0...127 1 0 Selection for syn-
chronizing require-
ment for reclosing
Auto initiation cnd
1=Not allowed
2=When sync fails
3=CB doesn't close
4=Both
2=When sync fails Auto initiation con-
dition
Tripping line 0...63 1 0 Tripping line,
defines INIT in-
puts which cause
OPEN_CB activa-
tion
Fourth delay in
SOTF
0=False
1=True
0=False Sets 4th delay into
use for all DEL_IN-
IT signals during
SOTF
First reclose time 0...300000 ms 10 5000 Dead time for CBB1
Second reclose
time
0...300000 ms 10 5000 Dead time for CBB2
Third reclose time 0...300000 ms 10 5000 Dead time for CBB3
Fourth reclose time 0...300000 ms 10 5000 Dead time for CBB4
Fifth reclose time 0...300000 ms 10 5000 Dead time for CBB5
Sixth reclose time 0...300000 ms 10 5000 Dead time for CBB6
Seventh reclose
time
0...300000 ms 10 5000 Dead time for CBB7
Table continues on the next page
Control functions 1MRS757644 H
1040 620 series
Technical Manual