7 Condition monitoring functions
7.1 Circuit breaker condition monitoring SSCBR
7.1.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
C37.2 device
number
Circuit-breaker condition moni-
toring
SSCBR CBCM CBCM
7.1.2 Function block
Figure 484: Function block
7.1.3 Functionality
The circuit-breaker condition monitoring function SSCBR is used to monitor
different parameters of the circuit breaker. The breaker requires maintenance when
the number of operations has reached a predefined value. The energy is calculated
from the measured input currents as a sum of I
y
t values. Alarms are generated
when the calculated values exceed the threshold settings.
The function contains a blocking functionality. It is possible to block the function
outputs, if desired.
1MRS757644 H
Condition monitoring functions
620 series
Technical Manual