Parameter Values (Range) Unit Step Default Description
Description SPCRGAPC1 Output
15
Generic control point description
Operation mode
0=Pulsed
1=Toggle/Persistent
-1=Off
-1=Off Operation mode for generic con-
trol point
Pulse length 10...3600000 ms 10 1000 Pulse length for pulsed operation
mode
Description SPCRGAPC1 Output
16
Generic control point description
3.17.13 Local generic control points SPCLGAPC
3.17.13.1 Function block
Figure 110: Function block
3.17.13.2 Functionality
The local generic control points function SPCLGAPC is dedicated only for local
controlling, that is, SPCLGAPC cannot be controlled remotely. The local control is
done through the buttons in the front panel.
3.17.13.3 Operation principle
The function can be enabled and disabled with the 
Operation
 setting. The
corresponding parameter values are "On" and "Off".
SPCLGAPC has the 
Operation mode
, 
Pulse length
 and 
Description
 settings available
to control all 16 outputs. By default, the 
Operation mode
 setting is set to "Off". This
disables the controllable signal output. SPCLGAPC also has a general setting 
Loc
Rem restriction
, which enables or disables the local or remote state functionality.
When the 
Operation mode
 is set to "Toggle", the corresponding output toggles
between "True" and "False" for every input pulse received. The state of the output is
stored in a nonvolatile memory and restored if the protection relay is restarted.
When the 
Operation mode
 is set to "Pulsed", the corresponding output can be used
to produce the predefined length of pulses. Once activated, the output remains
1MRS757644 H
Basic functions
620 series
Technical Manual
199